Last updated August 2, 2026
A-WALL-FULL-DIMS is not a code you have to memorise. It is four separate fields, each one a plain abbreviation, read left to right. Once you can see the fields, every layer name in a set of American drawings reads itself.
This is the AIA CAD Layer Format, which the United States National CAD Standard adopted and still carries. The standard itself costs money and is written for committees. The format underneath it is genuinely simple, and this page decodes it field by field with the full code tables.
The format

| Field | Characters | Required? | What it says |
|---|---|---|---|
| Discipline designator | 2 | Yes | Who drew it. The second character is a hyphen or a user-defined modifier |
| Major group | 4 | Yes | The building system. No customisation permitted |
| Minor group | 4 | Optional | Narrows the major group. Limited customisation permitted |
| Second minor group | 4 | Optional | NCS long format only — see below |
| Status | 1 | Optional | Phase of work. Always the last field |
The discipline code identifies the author of the graphic information, not the trade the object belongs to. That is the single most misunderstood rule in the whole standard: a structural column drawn by the architect is A-COLS, not S-COLS. It is how the same wall can legitimately appear as A-WALL in the architectural set and I-WALL in the interiors set.
Decoding A-WALL-FULL-DIMS
| Field | Value | Means |
|---|---|---|
| Discipline | A | Architectural |
| Major group | WALL | Walls |
| Minor group | FULL | Full height |
| Second minor group | DIMS | Dimensions |
A caveat worth knowing. That name has two minor groups, and the original AIA CAD Layer Guidelines define only one — in that version the fourth field is the status field, so A-WALL-FULL-DIMS would be reading DIMS as a status code, which it is not. The second minor group is part of the NCS long format, which lists four data fields as discipline designator, major group, two minor groups and status.
So if a layer name looks over-long against an older AIA chart, it is probably valid NCS rather than wrong. Both are below.
The same wall through the shorter forms
| Layer name | Reads as |
|---|---|
A-WALL | Architectural, walls. Major group only |
A-WALL-FULL | Architectural, walls, full height |
A-WALL-D | Architectural, walls, to be demolished. Status in the third field |
A-WALL-FULL-D | Architectural, full-height walls, to be demolished. Status in the fourth |
A-WALL-FULL-DIMS | Architectural, full-height walls, dimensions. NCS long format |
Discipline designators
| Code | Discipline | Code | Discipline |
|---|---|---|---|
A | Architectural | C | Civil |
E | Electrical | F | Fire Protection |
G | General | H | Hazardous Materials |
I | Interiors | L | Landscape |
M | Mechanical | P | Plumbing |
Q | Equipment | R | Resource |
S | Structural | T | Telecommunications |
X | Other | Z | Contractor / shop drawings |
Status field
| Code | Status | Code | Status |
|---|---|---|---|
N | New work | E | Existing to remain |
D | Existing to demolish | F | Future work |
T | Temporary work | M | Items to be moved |
R | Relocated items | X | Not in contract |
A remodelling plan typically carries A-WALL-N for new walls, A-WALL-E for existing to remain and A-WALL-D for walls coming out — three layers, one system, freezable independently.
Major group codes
Four characters, mandatory, and no customisation is allowed. This is the field that makes files from different offices interchangeable, which is the entire point of the standard.
| Code | Building system | Code | Building system |
|---|---|---|---|
ABLT | Anchor bolt | ACCS | Access |
ACID | Acid | ANNO | Annotation |
AREA | Area | BEAM | Beam |
BLDG | Building | BRIN | Brine systems |
CABL | Cable | CHIM | Chimney |
CLNG | Ceiling | CMPA | Compressed air systems |
CO2S | CO2 systems | CODE | Code |
COLS | Columns | COMM | Communications |
CONT | Controls | CWTR | Chilled water |
DECK | Floor decks | DETL | Detail |
DOMW | Domestic water | DUST | Dust |
ELEV | Elevation | ELHT | Electric heat |
ENER | Energy management | EQPM | Equipment |
EVAC | Evacuation | EXHS | Exhaust |
FIRE | Fire | FIXT | Fixture |
FLOR | Floor | FNDN | Foundation |
FUEL | Fuel | FURN | Furniture |
GLAZ | Glass | GRID | Grids |
GRND | Grounding | HALN | Halon |
HOTW | Hot water | HVAC | H.V.A.C. |
IGAS | Inert gas | IRRG | Irrigation |
JOIS | Joists | LGAS | Laboratory gas |
LITE | Lighting | LTNG | Lightning protection |
MACH | Machine shop | MDGS | Medical gas |
METL | Miscellaneous metal | NGAS | Natural gas |
NURS | Nursing | PGNG | Paging systems |
PIPE | Pipe | PKNG | Parking |
PLAN | Plans | PLNT | Plant |
POWR | Power | PROC | Process |
PROP | Property | PROT | Protection |
RCOV | Recover | REFG | Refrigeration |
RISR | Risers | ROAD | Road |
ROOF | Roof | SANR | Sanitary |
SECT | Sections | SERT | Security |
SITE | Site | SLAB | Slabs |
SOUN | Sound | SPCL | Special |
SPRN | Sprinklers | STAN | Standpipe systems |
STEM | Steam | STRM | Storm |
TEST | Test | TOPO | Topography |
TVAN | Television antenna | WALK | Walks |
WALL | Walls | WATR | Water |
XREF | External references |
Minor group codes
Four characters, optional, and limited customisation is allowed. The published list runs to roughly 200 entries; these are the ones that come up daily. The full AIA CAD Layer Format PDF has the rest.
| Code | Meaning | Code | Meaning |
|---|---|---|---|
CNTR | Centre lines | DIMS | Dimensions |
IDEN | Identification | KEYN | Key notes |
LEGN | Schedule, legend, table border | NOTE | Notes |
NPLT | Non-plotting information | OTLN | Outlines |
PATT | Textures and hatch patterns | SYMB | Symbols |
TEXT | Text | TTBL | Title blocks |
FULL | Full height | PRHT | Partial height |
PART | Partial height partition | MOVABLE | Movable |
FIXD | Fixed | FREE | Freestanding |
MOVE | Movable | EXTR | Exterior |
INTR | Interior | FIRE | Fire wall |
FH1H | One hour fire wall | FH2H | Two hour fire wall |
HEAD | Door and window headers | JAMB | Door and window jambs |
SILL | Sills | SWNG | Door swing arc |
GLAZ | Glazing | CASE | Casework |
STRS | Stairs, treads, escalators and ladders | HRAL | Stair and balcony handrails and guard rails |
LEVL | Level changes, ramps, pits and depressions | OPEN | Ceiling and roof openings |
SUSP | Suspended elements | RAIS | Raised |
EDGE | Edge of slab | JOIN | Slab control joints |
RBAR | Reinforcement | PILE | Piles, drilled piers |
COLS | Columns | GRID | Grid |
EQPM | Equipment | PFIX | Plumbing fixtures |
APPL | Appliances | FURN | Furniture |
PNLS | Furniture system panels | FILE | File cabinets |
SIGN | Signage | ADAG | Disabled access guides |
MCUT | Material cut by section | MBND | Material beyond section cut |
ELEV | Elevations | PLAN | Plans |
VPRT | Paper space viewports | ABAN | Abandoned |
NICN | Not in contract | MISC | Miscellaneous |
Annotation is the same in every discipline
Anything that is not a physical part of the building — text, dimensions, borders, detail references — goes in the ANNO major group. The same names are used whether the annotation sits in model space or paper space.
| Layer | Contains |
|---|---|
*-ANNO-DIMS | Dimensions |
*-ANNO-KEYN | Keynotes |
*-ANNO-LEGN | Legends and schedules |
*-ANNO-NOTE | Notes |
*-ANNO-NPLT | Construction lines, non-plotting information |
*-ANNO-REDL | Redline |
*-ANNO-REVS | Revisions |
*-ANNO-SYMB | Symbols |
*-ANNO-TEXT | Text |
*-ANNO-TTLB | Border and title block |
Dimensions, symbols and keynotes usually live in model space; legends, schedules, borders and title blocks in paper space. The layer names do not change between the two.
Elevations, sections and details
Each discipline gets its own groups for drawings that are not plans. The distinction between material cut by the section and material beyond it is what lets you give the cut line its own weight without touching anything else.
| Layer | Contains |
|---|---|
*-ELEV | Elevations |
*-ELEV-IDEN | Component identification numbers |
*-ELEV-OTLN | Building outlines |
*-ELEV-PATT | Textures and hatch patterns with different pens |
*-SECT | Sections |
*-SECT-IDEN | Component identification numbers |
*-SECT-MCUT | Material cut by section |
*-SECT-MBND | Material beyond section cut |
*-SECT-PATT | Textures and hatch patterns with different pens |
*-DETL | Details |
*-DETL-IDEN | Component identification numbers |
*-DETL-MCUT | Material cut by section |
*-DETL-MBND | Material beyond section cut |
*-DETL-PATT | Textures and hatch patterns with different pens |
Worked examples across the disciplines
| Layer name | Reads as |
|---|---|
A-DOOR-SWNG | Architectural · doors · swing arcs |
A-FLOR-STRS | Architectural · floor · stairs and treads |
A-WALL-FIRE | Architectural · walls · fire wall |
S-COLS-GRID | Structural · columns · grid |
S-SLAB-RBAR | Structural · slabs · reinforcement |
S-BEAM-DIMS | Structural · beams · dimensions |
M-HVAC-DUCT | Mechanical · HVAC · ductwork |
P-PIPE-DOMW | Plumbing · pipe · domestic water |
E-LITE-EMER | Electrical · lighting · emergency devices |
E-POWR-PANL | Electrical · power · panels |
F-SPRN-CLHD | Fire protection · sprinklers · ceiling heads |
C-TOPO-SPOT | Civil · topography · spot levels |
L-PLNT-GRND | Landscape · plants · ground covers |
T-COMM-JACK | Telecommunications · communications · jacks |
I-FURN-PNLS | Interiors · furniture · system panels |
A-ANNO-TTLB-N | Architectural · annotation · title block · new |
The other layer standard
The world runs two layer standards. AIA/NCS is used across North America and is a hierarchy of abbreviations: you read it like words. ISO 13567 is used across Europe and much of the rest of the world, and is a set of positional fields: you read it by counting characters.
| AIA / NCS | ISO 13567 | |
|---|---|---|
| Reads as | abbreviations | coded fields by position |
| Discipline | 1–2 characters, letters (A, S) | 2 characters, agent responsible |
| Element | 4-character major group (WALL) | classification code, often from a national table |
| Learning curve | low — the name is legible | higher — you need the field map |
| Extension | user modifiers in the discipline and minor fields | designed-in optional fields |
| Used in | North America | Europe, Australia and elsewhere |
If your office needs a third option, there is also the numbered layering system, which trades legibility for brevity.
The full format document
The AIA CAD Layer Format (PDF) — eight pages with the complete major and minor group listings, the annotation and view groups, and the methodology in full.
References
- The AIA CAD Layer Format — Methodology, the source for the field structure, discipline codes, status codes and the major and minor group listings on this page. draftsperson.net (PDF)
- United States National CAD Standard, CAD Layer Guidelines: Layer Name Format, published free by the NCS, for the long format’s two minor group fields and which fields are mandatory. nationalcadstandard.org
- United States National CAD Standard, overview and FAQs. nationalcadstandard.org
- ISO 13567 — CAD layer standard — the other half of the pair, field by field.
- Numbered CAD layering system — the shorthand alternative to both.